HTW-V61 series motorized valves(3-wire) are used to control the flow of hot water, chill water in heating, cooling or air-conditioning applications, so as to control room temperature indirectly. It consists of Actuator and Valve Body. The room temperature could be controlled in the set-point through turn-on or turn-off of valve.
Solenoid Valve 2/3 Way VC4043 Motorized Zone Valve For FCU Control SPST/SPDT HTW-V61
>> General
HTW-V61 series motorized valves(3-wire) are used to control the flow of hot water, chill water in heating, cooling or air-conditioning applications, so as to control room temperature indirectly. It consists of Actuator and Valve Body. The room temperature could be controlled in the set-point through turn-on or turn-off of valve.
>> Technical Parameters
•Consumption 5W
•Drive style Bi-direction reversible motor drive
•Cooperate time with thermostat the valve open within 6s at 60HZ
•N.W.(Kg)-Actuator 0.35
•Medium Cool/hot water
•Liquid temperature 1~95°C
•Pressure(MPa) 1.6
•Environment temperature 0~65°C the max relative humidity, non-condensing
•Storage temperature -20~65°C the max relative humidity, non-condensing
>> Models& Specifications of Valve Body
Model | Configuration | Kvs | Connection Type | Differential Pressure(MPa) |
HTW-V61-215 | normally closed two-way | 2 | G1/2 | 0.20 |
HTW-V61-220 | normally closed two-way | 3.2 | G3/4 | 0.10 |
HTW-V61-225 | normally closed two-way | 5.7 | G1 | 0.06 |
HTW-V61-315 | mixing three-way | 3.2 | G1/2 | 0.20 |
HTW-V61-320 | mixing three-way | 4.6 | G3/4 | 0.10 |
HTW-V61-325 | mixing three-way | 4.8 | G1 | 0.06 |